DPN MCB

DPN MCB

Contact Now
DPN MCB
DPN MCB
DPN MCB

1.General

1.1 Application 

For protecting cables and equipment against overload and short circuit. 

1.2 General rules for choosing MCB 

a.Technical data of the network at the point considered.The earthing systems(TNS,TNC),Short-circuit current at the circuit-breaker installation point,which must always be less than the breaking capacity of thru device,betwork normal voltage. 

b.There are 2 curve characteristics for KBHB magnetic operation. 

B.Curve (3-5 In) protection and control of the circuits against overloads and short-circuits,protection for people and big length cables in TN and IT systems. 

C.Curve (5-10 In) protection and control of the circuits against overloads and short-circuits,protection for resistive and inductive loads with low inrush current. 

2.Technical Information 

2.1 Curves 
DPN MCB 
 

  Standard   IEC/EN 60898-1
Electrical features Rated current In A 1,2,3,4,6,10,13,20,25,32,40
Poles   1P+N
Rated voltage Ue V 230
Insulation voltage Ui V 300
Rated frequency Hz 50/60
Rated breaking capacity A 4500/6000
Rated impulse withstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind. Freq. for 1 min kV 2
Pollution degree   2
Mechanical features Electrical life   4000
Mechanical life   10000
Contact position indicator   Yes
Protection degree   IP20
Reference temperature for setting of thermal element 30
Ambient temperature (with daily average ≤ 35℃)  -5...+40(Special application please refer to P32 for temperature compensation correction)
Storage temperation  -25...+70
Installation Terminal connection type   Cable/Pin-type busbar
Terminal size top/bottom for cable mm2 16
AWG  18 - 5
Terminal size top/bottom for busbar mm2 16
AWG  18 - 5
Tightening torque N*m 2
In-Ibs 18
Mounting   On DIN rail EN60715(35mm) by means of fast clip device
Connection   From top and bottom
Combination with accessories Auxiliary contact   Yes
Shunt release   Yes
Under voltage release   Yes
Alarm contant   Yes

2.3 Temperature derating 

Please refer to table below for temperature compensation correction 

Temperature  -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 55℃ 60℃
Temperature compensation coefficient 1.2 1.15 1.1 1.05 1 0.95 0.9 0.875 0.85

3. Overall and Mounting Dimensions(mm)

DPN MCB

DPN MCB.pdf