1.General
1.1 Application
For protecting cables and equipment against overload and short circuit.
1.2 General rules for choosing MCB
a.Technical data of the network at the point considered.The earthing systems(TNS,TNC),Short-circuit current at the circuit-breaker installation point,which must always be less than the breaking capacity of thru device,betwork normal voltage.
b.There are 2 curve characteristics for KBHB magnetic operation.
B.Curve (3-5 In) protection and control of the circuits against overloads and short-circuits,protection for people and big length cables in TN and IT systems.
C.Curve (5-10 In) protection and control of the circuits against overloads and short-circuits,protection for resistive and inductive loads with low inrush current.
2.Technical Information
2.1 Curves
Standard | IEC/EN 60898-1 | ||
Electrical features | Rated current In | A | 1,2,3,4,6,10,13,20,25,32,40 |
Poles | 1P+N | ||
Rated voltage Ue | V | 230 | |
Insulation voltage Ui | V | 300 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 4500/6000 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind. Freq. for 1 min | kV | 2 | |
Pollution degree | 2 | ||
Mechanical features | Electrical life | 4000 | |
Mechanical life | 10000 | ||
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Reference temperature for setting of thermal element | ℃ | 30 | |
Ambient temperature (with daily average ≤ 35℃) | ℃ | -5...+40(Special application please refer to P32 for temperature compensation correction) | |
Storage temperation | ℃ | -25...+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm2 | 16 | |
AWG | 18 - 5 | ||
Terminal size top/bottom for busbar | mm2 | 16 | |
AWG | 18 - 5 | ||
Tightening torque | N*m | 2 | |
In-Ibs | 18 | ||
Mounting | On DIN rail EN60715(35mm) by means of fast clip device | ||
Connection | From top and bottom | ||
Combination with accessories | Auxiliary contact | Yes | |
Shunt release | Yes | ||
Under voltage release | Yes | ||
Alarm contant | Yes |
2.3 Temperature derating
Please refer to table below for temperature compensation correction
Temperature | -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 55℃ | 60℃ |
Temperature compensation coefficient | 1.2 | 1.15 | 1.1 | 1.05 | 1 | 0.95 | 0.9 | 0.875 | 0.85 |